| Model | SLP-750VA | SLP-1K | SLP-1.5K | SLP-2K |  | SLP-3K | 
                    | Capacity (VA/W) | 750VA/500W | 1000VA/700W | 1.5000VA/1050W | 2000VA/1340W |  | 3000VA/2100W | 
                    | 1.INPUT | 
                    | Input Voltage | 
                    | Phase | Single Phase With Ground | 
                    | Nominal Input Voltages (Selectable) | 110V | 120V | 127V | 220V | 230V | 240V | 
                    | Transfer Voltage Range VAC (+4%~-4%) Based on load percentage | 
                    | Acceptable Input Voltage Range | 0 - 160 Vac | 0 - 300 VAC | 
                    | Line low Threshold | 88 | 96 | 102 | 176 | 184 | 192 | 
                    | Line low Comeback | 93 | 101 | 107 | 186 | 194 | 202 | 
                    | Line boost Threshold | 99 | 108 | 114 | 198 | 207 | 216 | 
                    | Line boost Comeback | 103 | 112 | 120 | 206 | 215 | 225 | 
                    | Line buck Comeback | 113 | 123 | 130 | 225 | 236 | 246 | 
                    | Line buck Threshold | 116 | 127 | 135 | 233 | 243 | 254 | 
                    | Line high Comeback | 127 | 139 | 147 | 254 | 266 | 278 | 
                    | Line high Threshold | 132 | 144 | 152 | 264 | 276 | 288 | 
                    | Input Frequency | Input frequency For 60 Hz units (auto selection ) | Input frequency For 50 Hz units (auto selection ) | 
                    | Default frequency (cold start) | 60HZ | 50 Hz | 
                    | Nominal Frequency | 50 Hz/60 Hz | 50 Hz/60 Hz | 
                    | Transfer Frequency | 60 Hz | 50 Hz | 
                    | Freq. Low Loss | 55 ± 0.1 Hz | 45 ± 0.1 Hz | 
                    | Freq. Low Comeback | 56 ± 0.1 Hz | 46 ± 0.1 Hz | 
                    | Freq. High Loss | 65 ± 0.1 Hz | 55 ± 0.1 Hz | 
                    | Freq. High Comeback | 64 ± 0.1 Hz | 54 ± 0.1 Hz | 
                    | Converter(Generator) | Support | 
                    | Freq. Low Loss | 40.0 ± 0.2 Hz | 
                    | Freq. Low Comeback | 42.0 ± 0.2 Hz | 
                    | Freq. High Loss | 70.0 ± 0.2 Hz | 
                    | Freq. High Comeback | 68.0 ± 0.2 Hz | 
                    | Input Power Factor | 
                    | Input Power Factor | ≥95%, Full RCD Load@ full PFC load and fully charged battery; boost and buck mode ≥ 92%. | 
                    | Input Protection | BREAKER +Software Protection | 
                    | 2.OUTPUT | 
                    | 1).On-Line Output | 
                    | Output Waveform | Sine wave, same as input | 
                    | Output Frequency Range | Same As Input Frequency | 
                    | Output Voltage regulation | 110V | 120V | 127 V | 220V | 230V | 240V | 
                    | Range (Outside of this range the units operates on Battery) 
 | 99~116 | 108~127 | 114 ~135 | 198~233 | 207~243 | 216~254 | 
                    | Boost Mode Voltage | 114% of Vin | 
                    | Buck Mode Voltage | 88 % of Vin | 
                    | Line Mode overload(SMPS Load) 
 
 | 110% -0%, +8%; fault after 3 minutes | 
                    | Line Mode overload(SMPS load) 
 | 150% -0%, +10%; fault after 10 cycles minimum | 
                    | 2.)Output, Inverter / Battery Mode | 
                    | Voltage Regulation | ± 5% of nominal; +5% ,-10% after Low Battery Warning | 
                    | Output Waveform | Sine wave | 
                    | Frequency Regulation | ±50/60±0.1 Hz | 
                    | Output Voltage Transient Response (Overshoot / Undershoot) (Battery mode with PFC type load) 
 | 0%-100%-0% Load; ±15 % max. 20%-100%-20% Load; ±8% max.
 
 | 
                    | Transient Recovery | To nominal voltage within 30ms. | 
                    | Output Voltage THD | At Low Battery Warning: 100% PFC Load < 5%THD; 100% NLL < 10% THD At Battery Cut Off: 100% PFC load < 10% THD; 100% NLL <15% THD 
 | 
                    | 3.Efficiency | >85 % at 100% NLL | 
                    | Short Circuit Protection | Active current limit; Shutoff within 300 ms. | 
                    | Battery Mode overload (SMPS load) | ≥ 110 % ± 6 %; fault after 30 seconds minimum | 
                    | ≥ 120 % ± 6 %; fault after 5 cycles minimum | 
                    | DC Component in the Output voltage | 10sec average < 0.1% of rms value of output voltage | 
                    | Load Take On | 150 msec; no load to 100 % RCD (8 mF/W) load to within 90 % of nominal output voltag | < 150 msec; no load to 100 % RCD (2 mF/W ) load to within 90 % of nominal output voltage | 
                    | Transfer Time | 2-4 msec typical, 6 msec max. | 
                    | 4.Short Circuit Protection |  |  |  |  |  |  | 
                    | Line Mode/ Battery Mode | Cut Off Output Within 300ms Then Fault | 
                    | 5.Battery |  |  |  |  |  |  | 
                    | Model | CL-750VA | CL-1K | CL-1.5K | CL-2K |  | CL-3K | 
                    | Capacity (VA/W) | 750VA/500W | 1000VA/700W | 1.5000VA/1050W | 2000VA/1340W |  | 3000VA/2100W | 
                    | OUTPUT | 24VDC | 48VDC | 96VDC | 
                    | Type/Capacity | CSB 12V/7AH | CSB 12V/9AH | CSB 12V7AH | CSB 12V9AH |  | CSB 12V/4.5AH | 
                    | Battery Quantity | 2PCS | 2PCS | 4PCS | 4PCS |  | 8PCS | 
                    | Backup Time | 5minutes | 5minutes | 5minutes | 5minutes |  | 5minutes | 
                    | (With full RCD load) | Alarm 2 minutes before it Shutdown | Alarm 2 minutes before it Shutdown | Alarm 2 minutes before it Shutdown | Alarm 2 minutes before it Shutdown |  | Alarm 2 minutes before it Shutdown | 
                    | Battery Protection | 
                    | Low Alarm Voltage (VDC) | 10.5±0.5V | 
                    | Low Alarm Comeback Voltage (VDC) | 11±0.5V | 
                    | Auto Shutdown Voltage (VDC) | 10±0.5V | 
                    | Battery Protection | 80A/Fuse | 50A/Fuse | 
                    | Battery Leakage | 200uA | 
                    | Battery Test | 
                    | Battery Fault | Transfer To Line Mode Immediately then alarm | 
                    | Default time | Every 30 days | 
                    | 6.Charger |  |  |  |  |  |  | 
                    | Fast Charge Voltage | 28.6~29.2vdc | 28.6~29.2vdc | 57.2~58.4vdc | 57.2~58.4vdc |  | 114.4~117.2vdc | 
                    | Float Charge Voltage | 26.8~27.6vdc | 26.8~27.6vdc | 53.6~55.2vdc | 53.6~55.2vdc |  | 107.2~111vdc | 
                    | Charging Current | 1.0A | 1.0A | 3.0A | 3.0A |  | 3.0A | 
                    | Charge Time | Internal battery modules will recharge less than 3 hours to 90% | 
                    | 7.Temperature-compensated | Yes | 
                    | 8.Controls and audio alarm |  |  |  |  |  |  | 
                    | Control |  |  |  |  |  |  | 
                    | Alarm Silence | Yes, In Battery Mode | 
                    | DC Power Start | Yes, In Battery Mode | 
                    | Auto Restart Function | Yes, In Line Mode | 
                    | Cooling | Force Air Cooling | 
                    | Audio Alarm |  |  |  |  |  |  | 
                    | Battery Mode | Beep/4 Sec | 
                    | Battery Low | Beep/1 Sec | 
                    | Battery Replacement | Beep/1 Sec |  | 
                    | UPS Fault | Continuous | 
                    | Over Load | Beep/1 Sec | 
                    |    |  |  |  |  |  |  | 
                    | Network Transient Protection | RJ45 | 
                    | Indicator | LCD/LED Indicator | 
                    | Communication |  |  |  |  |  |  | 
                    | SNMP Card | Webpower (Optional) | 
                    | USB | Standard (Optional) | 
                    | RS232 | Standard (DB9) | 
                    | EPO Function | Short circuit the EPO, the UPS will shutdown immediately | 
                    | Dry Contact | AS 400 card (optional) & DB9 | 
                    | 10. OPERATION ENVIRONMENT |  |  |  |  |  |  | 
                    | Acoustic Noise | ≤50dB | 
                    | Working Temperature | 0 ℃ to 40℃ | 
                    | (Long term use at ambient higher than 25°C reduces battery life) | 
                    | Transit Temperature | -20°C to +55 °C | 
                    | Storage Temperature | -20°C to +55 °C | 
                    | Humidity | <95% | 
                    | Altitudes |  |  |  |  |  |  | 
                    | Operating Altitude | 0-1500 meters@ 0-40°C/1501-3,000 meters @ 0-35 °C | 
                    | Non-Operating Altitude | 0 to 15,000 meters | 
                    | Products Size(mm) | 217*86.5*413.5 | 217*86.5*413.5 | 217*86.5*413.5 | 217*86.5*413.5 |  | 438*86.2*582 | 
                    | Products Weight(KG) | 15 | 16 | 23 | 23 |  | 34.1 |